题名 | Electrochemical effects on carbon steel in circulating cooling water systems: Scaling, corrosion and chemicals synergies |
作者 | |
通讯作者 | Li,Xiaoliang |
发表日期 | 2024-06-01
|
DOI | |
发表期刊 | |
ISSN | 2214-7144
|
卷号 | 63 |
摘要 | In cooling water systems balancing anti-scaling and simultaneous anti-corrosion effect on carbon steel needs to be addressed in applying electrochemical treatment procedure. This study investigated the impact of dosing corrosion inhibitors into electrochemical treatment process to achieve an optimized effect. An electrochemical unit equipped with Ti/RuO anode and Ti cathode was used in a simulated cooling water system. Initial results show that embedding a sole electrochemical system did reduce the scale deposition rate on the steel to about 20 %, and simultaneously change the crystalline form to a more readily removable aragonite-type, but promote an increase of corrosion rate to 65 % due to accelerated conversion of Fe to Fe on the surface of carbon steel. Three typical agents were selected to mitigate such adverse effect. It was shown that adding imidazoline and NaMoO could effectively mitigate the corrosive effects, but dosing HEDP had surprisingly led to an opposite consequence. The best performance achieved by dosing NaMoO was demonstrated due to the formation of surface film impedance on carbon steel which reduced its self-corrosion current density. Due to the electrochemical phosphorus recovery function, the phosphorus-containing corrosion inhibitor HEDP is deposited on the cathode plate. This deposition results in inadequate film formation on the surface of carbon steel, ultimately leading to an increase in the corrosion rate of carbon steel. The outcomes suggest that a combination of suitable corrosion inhibitor with electrochemical treatment procedure could be a new strategy in the application of such processes for simultaneous controlling scaling and corrosion. |
关键词 | |
相关链接 | [Scopus记录] |
收录类别 | |
语种 | 英语
|
学校署名 | 其他
|
Scopus记录号 | 2-s2.0-85193451329
|
来源库 | Scopus
|
引用统计 |
被引频次[WOS]:1
|
成果类型 | 期刊论文 |
条目标识符 | http://sustech.caswiz.com/handle/2SGJ60CL/761058 |
专题 | 南方科技大学 |
作者单位 | 1.State Key Laboratory of Eco-hydraulics in Northwest Arid Region,Xi'an University of Technology,Xi'an,710048,China 2.Sinopec Luoyang Company,Luoyang,471012,China 3.Melbourne Climate Futures Academy,Climate & Energy College,School of Geography,Earth and Atmospheric Sciences,The University of Melbourne,Melbourne,3010,Australia 4.Microelectronics Science and Engineering,School of Micro electronics,Southern University of Science and Technology,Shenzhen,518055,China 5.Northwest Engineering Corporation Limited,Xi'an,710048,China 6.Zhejiang University of Science and Technology,School of Environment and Natural Resource,Hangzhou,310018,China |
推荐引用方式 GB/T 7714 |
Lu,Sijia,Li,Xiaoliang,Zheng,Xing,et al. Electrochemical effects on carbon steel in circulating cooling water systems: Scaling, corrosion and chemicals synergies[J]. Journal of Water Process Engineering,2024,63.
|
APA |
Lu,Sijia.,Li,Xiaoliang.,Zheng,Xing.,Zhao,Huiyan.,Tian,Zhijuan.,...&Wu,Shizhang.(2024).Electrochemical effects on carbon steel in circulating cooling water systems: Scaling, corrosion and chemicals synergies.Journal of Water Process Engineering,63.
|
MLA |
Lu,Sijia,et al."Electrochemical effects on carbon steel in circulating cooling water systems: Scaling, corrosion and chemicals synergies".Journal of Water Process Engineering 63(2024).
|